1.0.1 This Code is formulated with a view to reasonably install and safely handle the building fire extinguisher (hereinafter referred to as "extinguisher"); effectively and timely extinguish fires, decrease fire losses and guarantee human and property security.
1.0.2 The Code is applicable to the installation, acceptance, inspection and maintenance of the extinguishers in industrial and civil buildings.
This Code is inapplicable to workshops or storehouses that produce and stock detonator, ammunition, hot working products and fireworks.
1.0.3 The installation, acceptance, inspection, and maintenance for extinguishers shall be in accordance with those specified current relevant standards of the nation beside this Code.
1 General Provision 2 Basic Requirements 2.1 Quality management 2.2 Materials and equipments 3 Installations 3.1 General requirements 3.2 Installation of portable extinguisher 3.3 Installation of wheeled extinguisher 3.4 Others 4 Acceptance check of distribution 4.1 General requirements 4.2 Acceptance check of distribution 4.3 Judgement rule for acceptance check of distribution 5 Checks and Service 5.1 General requirements 5.2 Check 5.3 Repair 5.4 Abandonment Appendix A Locating Encoding Table for the Extinguisher Distribution in Buildings Appendix B Classification and Acceptance Report for the Flawed Projects of the Extinguisher Distribution in Buildings Appendix C Content, Requirement, and Record of the Inspection of Extinguishers in Buildings
Standard
GB 50444-2008 Code for Acceptance and Inspection of Extinguisher Distribution in (English Version)
Standard No.
GB 50444-2008
Status
valid
Language
English
File Format
PDF
Word Count
5000 words
Price(USD)
120.0
Implemented on
2008-11-1
Delivery
via email in 1 business day
Detail of GB 50444-2008
Standard No.
GB 50444-2008
English Name
Code for Acceptance and Inspection of Extinguisher Distribution in
1.0.1 This Code is formulated with a view to reasonably install and safely handle the building fire extinguisher (hereinafter referred to as "extinguisher"); effectively and timely extinguish fires, decrease fire losses and guarantee human and property security.
1.0.2 The Code is applicable to the installation, acceptance, inspection and maintenance of the extinguishers in industrial and civil buildings.
This Code is inapplicable to workshops or storehouses that produce and stock detonator, ammunition, hot working products and fireworks.
1.0.3 The installation, acceptance, inspection, and maintenance for extinguishers shall be in accordance with those specified current relevant standards of the nation beside this Code.
Contents of GB 50444-2008
1 General Provision
2 Basic Requirements
2.1 Quality management
2.2 Materials and equipments
3 Installations
3.1 General requirements
3.2 Installation of portable extinguisher
3.3 Installation of wheeled extinguisher
3.4 Others
4 Acceptance check of distribution
4.1 General requirements
4.2 Acceptance check of distribution
4.3 Judgement rule for acceptance check of distribution
5 Checks and Service
5.1 General requirements
5.2 Check
5.3 Repair
5.4 Abandonment
Appendix A Locating Encoding Table for the Extinguisher Distribution in Buildings
Appendix B Classification and Acceptance Report for the Flawed Projects of the Extinguisher Distribution in Buildings
Appendix C Content, Requirement, and Record of the Inspection of Extinguishers in Buildings