1 Scope
This document defines the specific requirements for distribution boards intended to be operated by ordinary persons (abbreviated DBO, see 3.1.101) as follows:
—assemblies intended to be operated by ordinary persons (e.g. switching operations and replacing fuse-links), e.g. in domestic (household) applications;
—assemblies containing outgoing circuits with protective devices intended to be operated by ordinary persons... ....
—assemblies for applications where the nominal voltage to earth does not exceed 300 V AC (see Table G.1 in Annex G of GB/T 7251.1—2023);
NOTE 1: The voltage limits for DC applications are under consideration.
—assemblies with a rated current (Inc) of the outgoing circuits not exceeding 125 A and a rated current (InA) of the DBO not exceeding 250 A;
—assemblies intended for use in connection with the generation, transmission, distribution and conversion of electrical energy, and for the control of equipment consuming electrical energy and for associated data processing;
—enclosed, stationary assemblies;
—assemblies for indoor or outdoor use.
DBOs can contain protection devices, control devices, signalling devices alone or a combination of devices, e.g. circuit-breakers, load shedding relay, energy management, communication devices, lighting control.
This document does not apply to an empty enclosure nor to individual devices and self-contained components, such as circuit-breakers, fuse-switches, electronic equipment which comply with the relevant product standards. It describes the integration of devices, or self-contained components, or both, into a DBO or into an empty enclosure forming a DBO.
This document applies to DBOs designed, manufactured, and verified on a one-off basis or fully standardized and manufactured in quantity.
This document does not apply to the specific types of assemblies covered by other parts of the IEC 61439 series.
NOTE 2: Enclosures for electrical accessories for household and similar fixed electrical installations are covered in IEC 60670-24.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
Clause 2 of GB/T 7251.1—2023 is applicable in addition to the following.
Addition:
GB/T 7251.1—2023 Low-voltage switchgear and controlgear assemblies—Part 1: General rules (IEC 61439-1:2020, IDT)
IEC 60068-2-75 Environmental testing—Part 2-75: Tests—Test Eh: Hammer tests
NOTE: GB/T 2423.55—2023, Environmental testing—Part 2: Test methods—Test Eh: Hammer tests (IEC 60068-2-75:2014, IDT)
IEC 60269-3 Low-voltage fuses—Part 3: Supplementary requirements for fuses for operation by unskilled persons (fuses mainly for household and similar applications)—Examples of standardized systems of fuses A to F
NOTE: GB/T 13539.3—2017, Low-voltage fuses—Part 3: Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household and similar applications)—Examples of standardized systems of fuses A to F (IEC 60269-3:2013, IDT)
IEC 60364-8-82 Low-voltage electrical installations—Part 8-82: Functional aspects—Prosumer's low-voltage electrical installations
NOTE: GB/T 16895.37—2025, Low-voltage electrical installations—Part 8-82: Functional aspects—Prosumer's low-voltage electrical installations (IEC 60364-8-82:2022, IDT)
IEC 60669-2-4 Switches for household and similar fixed electrical installations—Part 2-4: Particular requirements—Isolating switches
NOTE: GB/T 16915.5—2012, Switches for household and similar fixed electrical installations—Part 2-4: Particular requirements—Isolating switches (IEC 60669-2-4:2004, IDT)
IEC 60898-1 Electrical accessories—Circuit-breakers for overcurrent protection for household and similar installations—Part 1: Circuit-breakers for a.c. operation
NOTE: GB/T 10963.1—2020, Electrical accessories—Circuit-breakers for overcurrent protection for household and similar installations—Part 1: Circuit-breakers for a.c. operation (IEC 60898-1:2015, IDT)
IEC 60947-2 Low-voltage switchgear and controlgear—Part 2: Circuit-breakers
NOTE: GB/T 14048.2—2020, Low-voltage switchgear and controlgear—Part 2: Circuit-breakers (IEC 60947-2:2019, MOD)
IEC 60947-3 Low-voltage switchgear and controlgear—Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
NOTE: GB/T 14048.3—2025, Low-voltage switchgear and controlgear—Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units (IEC 60947-3:2020, IDT)
IEC 61008 (all parts) Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs)
NOTE: GB/T 16916 (all parts), Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) [IEC 61008 (all parts)]
IEC 61009 (all parts) Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs)
NOTE: GB/T 16917 (all parts), Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) [IEC 61009 (all parts)]
IEC 62262 Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code)
NOTE: GB/T 20138—2023, Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code) (IEC 62262:2021, IDT)
IEC 62423:2009 Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses
NOTE: GB/T 22794—2017, Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses (IEC 62423:2009, IDT)
IEC 62606 General requirements for arc fault detection devices
NOTE: GB/T 31143—2025, General requirements for arc fault detection and protection devices (AFDD) (IEC 62606:2022, MOD)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in GB/T 7251.1—2023 and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
—IEC Electropedia: available at https://www.electropedia.org/
—ISO Online browsing platform: available at https://www.iso.org/obp
Clause 3 of GB/T 7251.1—2023 is applicable except as follows.
3.1 General terms
Additional terms and definitions:
3.1.101
distribution board intended to be operated by ordinary persons; DBO
assembly used to distribute and control electrical energy for all types of electrical supplies and loads, intended for operation by ordinary persons
Note 1 to entry: For operation by ordinary persons, see 8.4.6.1 of GB/T 7251.1—2023.
Note 2 to entry: Switching operations and replacing fuse-links are examples of operations intended to be carried out by ordinary persons.
Note 3 to entry: Definition 3.1.101 does not preclude the DBO from being operated by skilled or instructed persons, and also being used in non-domestic installations.
Note 4 to entry: DBOs can be assembled outside the factory of the original manufacturer. DBOs can be assembled by the original manufacturer or by an assembly manufacturer.
4 Symbols and abbreviations
Clause 4 of GB/T 7251.1—2023 is applicable.
5 Interface characteristics
Clause 5 of GB/T 7251.1—2023 is applicable except as follows.
5.1 General
Addition:
This objective can be achieved through one of two typical processes; the user will either select a catalogue product, the characteristics of which meet the required user needs, or make a specific agreement with the manufacturer.
In both cases, the specification schedule according to Annex AA is intended to help the user to provide all data necessary to specify, and to help the manufacturer to provide the actual DBO characteristics. In some cases information declared by the DBO manufacturer may take the place of an agreement.
5.2.4 Rated impulse withstand voltage (Uimp) (of the assembly)
Replacement:
The rated impulse withstand voltage of the assembly shall be equal to or higher than the values stated for the transient overvoltages occurring in the electrical system(s) to which the circuit is designed to be connected.
DBOs shall comply with a minimum overvoltage category III (see IEC 60364-4-44) according to Table G.1 of GB/T 7251.1—2023.
5.3.1 Rated current of an assembly (InA)
Addition:
See Annex CC for examples of when a generator, for example a photovoltaic system, wind turbine, battery is used as additional source(s) of supply in parallel with another source that is connected to the DBO.
5.4 Rated diversity factor (RDF)
Addition:
In the absence of an agreement between the DBO manufacturer and user concerning the actual load currents, the type of load, the assumed loading of the outgoing circuits of the DBO or group of outgoing circuits can be based on the values in Table 101.
The assumed load current is the rated current of the protective device In, as required by the user, multiplied with the assumed loading factor of Table 101.
NOTE 101: The rated current In of a protective device is defined in their product standard.
6 Information
Clause 6 of GB/T 7251.1—2023 is applicable except as follows.
6.1 Assembly designation marking
Addition to the first paragraph:
The test of 10.2.7.1 only applies to DBOs intended for outdoor installation.
Addition of the following new item:
h) degree of protection if greater than IP2XC.
6.2.2 Instructions for handling, installation, operation and maintenance
Addition to the first paragraph:
The original or assembly manufacturer shall provide in their documentation, any routine verification required to be carried out by the installer for the DBO to conform to IEC 61439-3.
6.3 Device and/or component identification
Addition:
For RCDs supplying more than one final circuit, it shall be possible for ordinary persons to identify which outgoing circuits the RCD supplies, for example when the RCD is adjacent to the outgoing group of circuits it supplies or by providing labels for the installer to apply to the DBO after installation. The identification means shall be visible without accessing live parts.
7 Service conditions
Clause 7 of GB/T 7251.1—2023 is applicable except as follows.
7.1.2 Pollution degree
Addition:
A minimum pollution degree 2 applies.
7.2 Special service conditions
Addition:
NOTE 101: The effects upon a DBO design and related ratings, instructions, etc. when used in a prosumer's electrical installation (PEI) can take account of the relevant requirements in IEC 60364-8-82. See Annex BB.
8 Constructional requirements
Clause 8 of GB/T 7251.1—2023 is applicable except as follows.
8.1.3.2.2 Resistance of insulating materials to normal heat
Addition:
NOTE 101: This Subclause 8.1.3.2.2 also applies to covers and enclosures made of insulating materials.
8.2.1 Protection against mechanical impact (IK code)
Replacement:
Standard
GB/T 7251.3-2026 Low-voltage switchgear and controlgear assemblies—Part 3:Distribution boards intended to be operated by ordinary persons(DBO) (English)
Standard No.
GB/T 7251.3-2026
Status
to be valid
Language
English
File Format
PDF
Word Count
18500 words
Translation Price(USD)
490.0
Implemented on
2027-4-1
Delivery
via email in 1~3 business day
Detail of GB/T 7251.3-2026
Standard No.
GB/T 7251.3-2026
English Name
Low-voltage switchgear and controlgear assemblies—Part 3:Distribution boards intended to be operated by ordinary persons(DBO)
GB/T 7251.3-2026 Low-voltage switchgear and controlgear assemblies—Part 3:Distribution boards intended to be operated by ordinary persons(DBO)
1 Scope
This document defines the specific requirements for distribution boards intended to be operated by ordinary persons (abbreviated DBO, see 3.1.101) as follows:
—assemblies intended to be operated by ordinary persons (e.g. switching operations and replacing fuse-links), e.g. in domestic (household) applications;
—assemblies containing outgoing circuits with protective devices intended to be operated by ordinary persons... ....
—assemblies for applications where the nominal voltage to earth does not exceed 300 V AC (see Table G.1 in Annex G of GB/T 7251.1—2023);
NOTE 1: The voltage limits for DC applications are under consideration.
—assemblies with a rated current (Inc) of the outgoing circuits not exceeding 125 A and a rated current (InA) of the DBO not exceeding 250 A;
—assemblies intended for use in connection with the generation, transmission, distribution and conversion of electrical energy, and for the control of equipment consuming electrical energy and for associated data processing;
—enclosed, stationary assemblies;
—assemblies for indoor or outdoor use.
DBOs can contain protection devices, control devices, signalling devices alone or a combination of devices, e.g. circuit-breakers, load shedding relay, energy management, communication devices, lighting control.
This document does not apply to an empty enclosure nor to individual devices and self-contained components, such as circuit-breakers, fuse-switches, electronic equipment which comply with the relevant product standards. It describes the integration of devices, or self-contained components, or both, into a DBO or into an empty enclosure forming a DBO.
This document applies to DBOs designed, manufactured, and verified on a one-off basis or fully standardized and manufactured in quantity.
This document does not apply to the specific types of assemblies covered by other parts of the IEC 61439 series.
NOTE 2: Enclosures for electrical accessories for household and similar fixed electrical installations are covered in IEC 60670-24.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
Clause 2 of GB/T 7251.1—2023 is applicable in addition to the following.
Addition:
GB/T 7251.1—2023 Low-voltage switchgear and controlgear assemblies—Part 1: General rules (IEC 61439-1:2020, IDT)
IEC 60068-2-75 Environmental testing—Part 2-75: Tests—Test Eh: Hammer tests
NOTE: GB/T 2423.55—2023, Environmental testing—Part 2: Test methods—Test Eh: Hammer tests (IEC 60068-2-75:2014, IDT)
IEC 60269-3 Low-voltage fuses—Part 3: Supplementary requirements for fuses for operation by unskilled persons (fuses mainly for household and similar applications)—Examples of standardized systems of fuses A to F
NOTE: GB/T 13539.3—2017, Low-voltage fuses—Part 3: Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household and similar applications)—Examples of standardized systems of fuses A to F (IEC 60269-3:2013, IDT)
IEC 60364-8-82 Low-voltage electrical installations—Part 8-82: Functional aspects—Prosumer's low-voltage electrical installations
NOTE: GB/T 16895.37—2025, Low-voltage electrical installations—Part 8-82: Functional aspects—Prosumer's low-voltage electrical installations (IEC 60364-8-82:2022, IDT)
IEC 60669-2-4 Switches for household and similar fixed electrical installations—Part 2-4: Particular requirements—Isolating switches
NOTE: GB/T 16915.5—2012, Switches for household and similar fixed electrical installations—Part 2-4: Particular requirements—Isolating switches (IEC 60669-2-4:2004, IDT)
IEC 60898-1 Electrical accessories—Circuit-breakers for overcurrent protection for household and similar installations—Part 1: Circuit-breakers for a.c. operation
NOTE: GB/T 10963.1—2020, Electrical accessories—Circuit-breakers for overcurrent protection for household and similar installations—Part 1: Circuit-breakers for a.c. operation (IEC 60898-1:2015, IDT)
IEC 60947-2 Low-voltage switchgear and controlgear—Part 2: Circuit-breakers
NOTE: GB/T 14048.2—2020, Low-voltage switchgear and controlgear—Part 2: Circuit-breakers (IEC 60947-2:2019, MOD)
IEC 60947-3 Low-voltage switchgear and controlgear—Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
NOTE: GB/T 14048.3—2025, Low-voltage switchgear and controlgear—Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units (IEC 60947-3:2020, IDT)
IEC 61008 (all parts) Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs)
NOTE: GB/T 16916 (all parts), Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) [IEC 61008 (all parts)]
IEC 61009 (all parts) Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs)
NOTE: GB/T 16917 (all parts), Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) [IEC 61009 (all parts)]
IEC 62262 Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code)
NOTE: GB/T 20138—2023, Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code) (IEC 62262:2021, IDT)
IEC 62423:2009 Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses
NOTE: GB/T 22794—2017, Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses (IEC 62423:2009, IDT)
IEC 62606 General requirements for arc fault detection devices
NOTE: GB/T 31143—2025, General requirements for arc fault detection and protection devices (AFDD) (IEC 62606:2022, MOD)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in GB/T 7251.1—2023 and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
—IEC Electropedia: available at https://www.electropedia.org/
—ISO Online browsing platform: available at https://www.iso.org/obp
Clause 3 of GB/T 7251.1—2023 is applicable except as follows.
3.1 General terms
Additional terms and definitions:
3.1.101
distribution board intended to be operated by ordinary persons; DBO
assembly used to distribute and control electrical energy for all types of electrical supplies and loads, intended for operation by ordinary persons
Note 1 to entry: For operation by ordinary persons, see 8.4.6.1 of GB/T 7251.1—2023.
Note 2 to entry: Switching operations and replacing fuse-links are examples of operations intended to be carried out by ordinary persons.
Note 3 to entry: Definition 3.1.101 does not preclude the DBO from being operated by skilled or instructed persons, and also being used in non-domestic installations.
Note 4 to entry: DBOs can be assembled outside the factory of the original manufacturer. DBOs can be assembled by the original manufacturer or by an assembly manufacturer.
4 Symbols and abbreviations
Clause 4 of GB/T 7251.1—2023 is applicable.
5 Interface characteristics
Clause 5 of GB/T 7251.1—2023 is applicable except as follows.
5.1 General
Addition:
This objective can be achieved through one of two typical processes; the user will either select a catalogue product, the characteristics of which meet the required user needs, or make a specific agreement with the manufacturer.
In both cases, the specification schedule according to Annex AA is intended to help the user to provide all data necessary to specify, and to help the manufacturer to provide the actual DBO characteristics. In some cases information declared by the DBO manufacturer may take the place of an agreement.
5.2.4 Rated impulse withstand voltage (Uimp) (of the assembly)
Replacement:
The rated impulse withstand voltage of the assembly shall be equal to or higher than the values stated for the transient overvoltages occurring in the electrical system(s) to which the circuit is designed to be connected.
DBOs shall comply with a minimum overvoltage category III (see IEC 60364-4-44) according to Table G.1 of GB/T 7251.1—2023.
5.3.1 Rated current of an assembly (InA)
Addition:
See Annex CC for examples of when a generator, for example a photovoltaic system, wind turbine, battery is used as additional source(s) of supply in parallel with another source that is connected to the DBO.
5.4 Rated diversity factor (RDF)
Addition:
In the absence of an agreement between the DBO manufacturer and user concerning the actual load currents, the type of load, the assumed loading of the outgoing circuits of the DBO or group of outgoing circuits can be based on the values in Table 101.
The assumed load current is the rated current of the protective device In, as required by the user, multiplied with the assumed loading factor of Table 101.
NOTE 101: The rated current In of a protective device is defined in their product standard.
6 Information
Clause 6 of GB/T 7251.1—2023 is applicable except as follows.
6.1 Assembly designation marking
Addition to the first paragraph:
The test of 10.2.7.1 only applies to DBOs intended for outdoor installation.
Addition of the following new item:
h) degree of protection if greater than IP2XC.
6.2.2 Instructions for handling, installation, operation and maintenance
Addition to the first paragraph:
The original or assembly manufacturer shall provide in their documentation, any routine verification required to be carried out by the installer for the DBO to conform to IEC 61439-3.
6.3 Device and/or component identification
Addition:
For RCDs supplying more than one final circuit, it shall be possible for ordinary persons to identify which outgoing circuits the RCD supplies, for example when the RCD is adjacent to the outgoing group of circuits it supplies or by providing labels for the installer to apply to the DBO after installation. The identification means shall be visible without accessing live parts.
7 Service conditions
Clause 7 of GB/T 7251.1—2023 is applicable except as follows.
7.1.2 Pollution degree
Addition:
A minimum pollution degree 2 applies.
7.2 Special service conditions
Addition:
NOTE 101: The effects upon a DBO design and related ratings, instructions, etc. when used in a prosumer's electrical installation (PEI) can take account of the relevant requirements in IEC 60364-8-82. See Annex BB.
8 Constructional requirements
Clause 8 of GB/T 7251.1—2023 is applicable except as follows.
8.1.3.2.2 Resistance of insulating materials to normal heat
Addition:
NOTE 101: This Subclause 8.1.3.2.2 also applies to covers and enclosures made of insulating materials.
8.2.1 Protection against mechanical impact (IK code)
Replacement: