GB/T 47667-2026 Bypass thyristors of converter valves for high-voltage direct current power transmission using voltage sourced converters English, Anglais, Englisch, Inglés, えいご
This is a draft translation for reference among interesting stakeholders. The finalized translation (passing through draft translation, self-check, revision and verification) will be delivered upon being ordered.
ICS
CCS
National Standard of the People's Republic of China
GB/T 47667-2026
Bypass thyristors of converter valves for high-voltage direct current power transmission using voltage sourced converters
柔性直流输电换流阀用旁路晶闸管
Issue date: 2026-02-27 Implementation date: 2026-09-01
Issued by the General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China
the Standardization Administration of the People's Republic of China
Contents
Foreword
1 Scope
2 Normative references
3 Terms and definitions
4 Classification, function and characteristics
5 Ratings (limiting values) and characteristics
6 Routine tests
7 Type tests
8 Data sheets, marking, packaging and storage
Annex A (informative) Function of bypass thyristors in sub-modules
Annex B (informative) Examples of sub-module topologies with bypass thyristors and their functions
Bibliography
Bypass thyristors for flexible DC transmission converter valves
1 Scope
This document defines the terms for bypass thyristors for flexible DC transmission converter valves, specifies the ratings (limiting values) and characteristics requirements, as well as marking, packaging and storage, and describes the methods for routine tests and type tests.
This document is applicable to bypass thyristors for sub-modules of flexible DC transmission converter valves. Bypass thyristors for other voltage-source power electronic equipment may refer to this document.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition (including any amendments) applies.
GB/T 2900.66, Electrotechnical terminology — Semiconductor devices and integrated circuits
GB/T 13384, General specifications for packaging of mechanical and electrical products
GB/T 15291-2015, Semiconductor devices — Part 6: Thyristors
GB/T 17573, Semiconductor devices — Discrete devices and integrated circuits — Part 1: General
GB/T 33348-2024, Voltage sourced converter valves for high-voltage direct current (HVDC) power transmission — Electrical testing
GB/T 40865-2021, Terminology of flexible direct current transmission
IEC 60747-6:2025, Semiconductor devices — Part 6: Discrete devices — Thyristors
3 Terms and definitions
For the purposes of this document, the terms and definitions given in GB/T 2900.66, GB/T 17573 and GB/T 40865-2021, as well as the following, apply.
3.1 Terms related to bypass thyristors
3.1.1
bypass thyristor
One of the components of a sub-module of a flexible DC transmission converter valve, used to reduce the transient current stress on the freewheeling diode and/or to provide a current path when the sub-module requires bypassing.
[Source: GB/T 40865-2021, 7.21, modified]
3.1.2
conventional bypass thyristor
A bypass thyristor that can be triggered into conduction in the forward direction and exhibits a blocking state in the reverse direction.
3.1.3
unidirectional breakdown bypass thyristor
A bypass thyristor that can break down within a preset reverse breakdown voltage range and, after breakdown, exhibits a low-impedance state.
3.1.4
bidirectional breakdown bypass thyristor
A bypass thyristor that can break down within a preset bidirectional breakdown voltage range and, after breakdown in either direction, exhibits a low-impedance state.
Note: The graphical symbol is shown in Figure 1.
3.2 Terms related to flexible DC transmission
3.2.1
sub-module (SM)
A standard component constituting a modular multilevel converter, which can be selected with different topological structures according to requirements.
[Source: GB/T 40865-2021, 7.10]
3.2.2
valve section
An electrical combination (assembly) consisting of several valve levels and other components, used for testing purposes, proportionally representing the electrical performance of the complete valve.
[Source: GB/T 33348-2024, 3.5.4]
3.2.3
sub-module fault bypass
When a fault exists inside a sub-module, to prevent affecting the normal operation of the converter, the sub-module is bypassed by its protective components, and the converter bridge arm current flows through the bypass path.
[Source: GB/T 40865-2021, 5.23.3, modified]
3.3 Terms for ratings and characteristics: Principal voltages
3.3.1
bypass break-over voltage (VBBO)
The transient voltage at which, when applied to a unidirectional or bidirectional breakdown bypass thyristor, it enters a state of amplified current flow. Upon removal and reapplication of voltage, the voltage across its terminals is re-established and the blocking characteristic is maintained.
Note: If the voltage is controlled after break-over, the unidirectional or bidirectional breakdown bypass thyristor itself will not be damaged by the break-over.
3.3.2
bypass breakdown voltage (VBBR)
The transient voltage at which, when applied to a unidirectional or bidirectional breakdown bypass thyristor, it enters a state of amplified current flow. Upon removal and reapplication of voltage, the voltage across its terminals cannot be re-established and the conducting characteristic is maintained.
Note: Unidirectional and bidirectional breakdown bypass thyristors applied with bypass breakdown voltage will be damaged and exhibit a low-impedance state after breakdown.
3.4 Terms for ratings and characteristics: Principal currents
3.4.1
non-repetitive surge on-state current (ITSM)
A pulsed on-state current of short duration and specified waveform.
Note: This current is caused by abnormal circuit conditions, resulting in the junction temperature exceeding or possibly exceeding the rated maximum equivalent junction temperature, but it occurs very infrequently and has a limited number of occurrences during the device's service life.
[Source: IEC 60747-6:2025, 3.3.1, modified]
3.4.2
multi-cycle surge current (ITSMM)
The converter valve bridge arm current caused by a fault (such as a DC-side short circuit in a flexible DC transmission system), having a multi-cycle waveform and lasting for multiple power frequency cycles.
Note: The specific number of cycles is determined by the project. Taking five cycles as an example, see Figure 2.
[Source: GB/T 37660-2019, 3.2, modified]
3.4.3
I²t value
The integral of the square of the surge current over the duration of the current surge, where the integration time titi is the duration of the surge current.
Note: The I²t value is given by Formula (1).
[Source: IEC 60747-6:2025, 3.3.2, modified]
Standard
GB/T 47667-2026 Bypass thyristors of converter valves for high-voltage direct current power transmission using voltage sourced converters (English)
Standard No.
GB/T 47667-2026
Status
to be valid
Language
English
File Format
PDF
Word Count
17000 words
Translation Price(USD)
510.0
Implemented on
2027-2-1
Delivery
via email in 1~5 business day
Detail of GB/T 47667-2026
Standard No.
GB/T 47667-2026
English Name
Bypass thyristors of converter valves for high-voltage direct current power transmission using voltage sourced converters
GB/T 47667-2026 Bypass thyristors of converter valves for high-voltage direct current power transmission using voltage sourced converters English, Anglais, Englisch, Inglés, えいご
This is a draft translation for reference among interesting stakeholders. The finalized translation (passing through draft translation, self-check, revision and verification) will be delivered upon being ordered.
ICS
CCS
National Standard of the People's Republic of China
GB/T 47667-2026
Bypass thyristors of converter valves for high-voltage direct current power transmission using voltage sourced converters
柔性直流输电换流阀用旁路晶闸管
Issue date: 2026-02-27 Implementation date: 2026-09-01
Issued by the General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China
the Standardization Administration of the People's Republic of China
Contents
Foreword
1 Scope
2 Normative references
3 Terms and definitions
4 Classification, function and characteristics
5 Ratings (limiting values) and characteristics
6 Routine tests
7 Type tests
8 Data sheets, marking, packaging and storage
Annex A (informative) Function of bypass thyristors in sub-modules
Annex B (informative) Examples of sub-module topologies with bypass thyristors and their functions
Bibliography
Bypass thyristors for flexible DC transmission converter valves
1 Scope
This document defines the terms for bypass thyristors for flexible DC transmission converter valves, specifies the ratings (limiting values) and characteristics requirements, as well as marking, packaging and storage, and describes the methods for routine tests and type tests.
This document is applicable to bypass thyristors for sub-modules of flexible DC transmission converter valves. Bypass thyristors for other voltage-source power electronic equipment may refer to this document.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition (including any amendments) applies.
GB/T 2900.66, Electrotechnical terminology — Semiconductor devices and integrated circuits
GB/T 13384, General specifications for packaging of mechanical and electrical products
GB/T 15291-2015, Semiconductor devices — Part 6: Thyristors
GB/T 17573, Semiconductor devices — Discrete devices and integrated circuits — Part 1: General
GB/T 33348-2024, Voltage sourced converter valves for high-voltage direct current (HVDC) power transmission — Electrical testing
GB/T 40865-2021, Terminology of flexible direct current transmission
IEC 60747-6:2025, Semiconductor devices — Part 6: Discrete devices — Thyristors
3 Terms and definitions
For the purposes of this document, the terms and definitions given in GB/T 2900.66, GB/T 17573 and GB/T 40865-2021, as well as the following, apply.
3.1 Terms related to bypass thyristors
3.1.1
bypass thyristor
One of the components of a sub-module of a flexible DC transmission converter valve, used to reduce the transient current stress on the freewheeling diode and/or to provide a current path when the sub-module requires bypassing.
[Source: GB/T 40865-2021, 7.21, modified]
3.1.2
conventional bypass thyristor
A bypass thyristor that can be triggered into conduction in the forward direction and exhibits a blocking state in the reverse direction.
3.1.3
unidirectional breakdown bypass thyristor
A bypass thyristor that can break down within a preset reverse breakdown voltage range and, after breakdown, exhibits a low-impedance state.
3.1.4
bidirectional breakdown bypass thyristor
A bypass thyristor that can break down within a preset bidirectional breakdown voltage range and, after breakdown in either direction, exhibits a low-impedance state.
Note: The graphical symbol is shown in Figure 1.
3.2 Terms related to flexible DC transmission
3.2.1
sub-module (SM)
A standard component constituting a modular multilevel converter, which can be selected with different topological structures according to requirements.
[Source: GB/T 40865-2021, 7.10]
3.2.2
valve section
An electrical combination (assembly) consisting of several valve levels and other components, used for testing purposes, proportionally representing the electrical performance of the complete valve.
[Source: GB/T 33348-2024, 3.5.4]
3.2.3
sub-module fault bypass
When a fault exists inside a sub-module, to prevent affecting the normal operation of the converter, the sub-module is bypassed by its protective components, and the converter bridge arm current flows through the bypass path.
[Source: GB/T 40865-2021, 5.23.3, modified]
3.3 Terms for ratings and characteristics: Principal voltages
3.3.1
bypass break-over voltage (VBBO)
The transient voltage at which, when applied to a unidirectional or bidirectional breakdown bypass thyristor, it enters a state of amplified current flow. Upon removal and reapplication of voltage, the voltage across its terminals is re-established and the blocking characteristic is maintained.
Note: If the voltage is controlled after break-over, the unidirectional or bidirectional breakdown bypass thyristor itself will not be damaged by the break-over.
3.3.2
bypass breakdown voltage (VBBR)
The transient voltage at which, when applied to a unidirectional or bidirectional breakdown bypass thyristor, it enters a state of amplified current flow. Upon removal and reapplication of voltage, the voltage across its terminals cannot be re-established and the conducting characteristic is maintained.
Note: Unidirectional and bidirectional breakdown bypass thyristors applied with bypass breakdown voltage will be damaged and exhibit a low-impedance state after breakdown.
3.4 Terms for ratings and characteristics: Principal currents
3.4.1
non-repetitive surge on-state current (ITSM)
A pulsed on-state current of short duration and specified waveform.
Note: This current is caused by abnormal circuit conditions, resulting in the junction temperature exceeding or possibly exceeding the rated maximum equivalent junction temperature, but it occurs very infrequently and has a limited number of occurrences during the device's service life.
[Source: IEC 60747-6:2025, 3.3.1, modified]
3.4.2
multi-cycle surge current (ITSMM)
The converter valve bridge arm current caused by a fault (such as a DC-side short circuit in a flexible DC transmission system), having a multi-cycle waveform and lasting for multiple power frequency cycles.
Note: The specific number of cycles is determined by the project. Taking five cycles as an example, see Figure 2.
[Source: GB/T 37660-2019, 3.2, modified]
3.4.3
I²t value
The integral of the square of the surge current over the duration of the current surge, where the integration time titi is the duration of the surge current.
Note: The I²t value is given by Formula (1).
[Source: IEC 60747-6:2025, 3.3.2, modified]